Sign In | Join Free | My burrillandco.com
Home > Temperature Transmitters >

Loop-powered Pt100 converter with excellent accuracy and selectable response time PR 3333

Shaanxi Qindiyuan Environmental Protection Equipment Co., Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap Loop-powered Pt100 converter with excellent accuracy and selectable response time PR 3333 from wholesalers
     
    Buy cheap Loop-powered Pt100 converter with excellent accuracy and selectable response time PR 3333 from wholesalers
    • Buy cheap Loop-powered Pt100 converter with excellent accuracy and selectable response time PR 3333 from wholesalers
    • Buy cheap Loop-powered Pt100 converter with excellent accuracy and selectable response time PR 3333 from wholesalers
    • Buy cheap Loop-powered Pt100 converter with excellent accuracy and selectable response time PR 3333 from wholesalers
    • Buy cheap Loop-powered Pt100 converter with excellent accuracy and selectable response time PR 3333 from wholesalers

    Loop-powered Pt100 converter with excellent accuracy and selectable response time PR 3333

    Ask Lasest Price
    Brand Name : PR
    Model Number : PR 3333
    Certification : CO
    Price : 200-450usd
    Payment Terms : T/T
    Supply Ability : 99pcs 4-6 weeks
    Delivery Time : 5-7 work days
    • Product Details
    • Company Profile

    Loop-powered Pt100 converter with excellent accuracy and selectable response time PR 3333

    Pt100 Converter, Loop-Powered
    PR 3333
    Excellent accuracy, better than 0.1% of span
    Excellent EMC performance and 50/60 Hz noise suppression
    Selectable < 30 ms / 300 ms response time
    Pre-calibrated for immediate use
    Environmental Conditions
    Operating temperature-25°C to +70°C
    Storage temperature-40°C to +85°C
    Calibration temperature20...28°C
    Relative humidity< 95% RH (non-condensing)
    Protection degreeIP20
    Installation environmentPollution degree 2 & measurement/overvoltage category II
    Mechanical Specifications
    Dimensions (HxWxD)113 x 6.1 x 115 mm
    Weight approx.70 g
    DIN rail typeDIN EN 60715/35 mm
    Wire size0.13...2.5 mm² / AWG 26...12 stranded wire
    Screw terminal torque0.5 Nm
    Vibration complianceIEC 60068-2-6
    • 2...25 Hz: ±1.6 mm
    • 25...100 Hz: ±4 g
    Technical Specifications
    Power Supply
    Supply voltage3.3...35 VDC
    Max. required power0.80 W
    Internal power dissipation12 mW...0.8 W
    Performance Characteristics
    Response time (0...90%, 100...10%)< 30 ms / 300 ms (selectable)
    Voltage drop3.3 VDC
    Signal / noise ratioMin. 60 dB
    ProgrammingDIP switches
    Signal dynamics, input23 bit
    Signal dynamics, output18 bit
    EMC immunity influence< ±0.5% of span
    Extended EMC immunity< ±1% of span (NAMUR NE21, A criterion, burst)
    Incorrect DIP-switch setting identification3.5 mA
    Input Specifications
    RTD Input
    Temperature range, Pt100-200...+850°C
    Min. measurement range (span)10°C
    AccuracyBetter than 0.1% of span or 0.2°C
    Temperature coefficient0.02°C/°C or ≤ ±0.01%/°C
    Sensor current< 150 µA
    Sensor cable resistance< 50 Ω per wire
    Effect of sensor cable resistance (3-/4-wire)< 0.002 Ω / Ω
    Sensor error detectionYes - selectable via DIP-switch
    Broken sensor detection> 800 Ω
    Shorted sensor detection< 18 Ω
    Output Specifications
    Updating time10 ms
    Programmable signal ranges4...20 and 20...4 mA
    Load (@ current output)≤ (Vsupply - 3.3) / 0.023 [Ω]
    Load stability≤ 0.01% of span / 100 Ω
    Sensor error indication3.5 mA or 23 mA / according to NAMUR NE43 or OFF
    Intrinsic Safety & Ex Markings
    ATEXII 3 G Ex ec IIC T4 Gc
    IECExEx ec IIC T4 Gc
    FM, USCl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4
    FM, CACl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4
    EAC Ex2Ex nA IIC T4 Gc X
    Compliance & Standards
    EMC2014/30/EU & UK SI 2016/1091
    LVD2014/35/EU & UK SI 2016/1101
    ATEX2014/34/EU & UK SI 2016/1107
    RoHS2011/65/EU & UK SI 2012/3032
    EACTR-CU 020/2011
    EAC ExTR-CU 012/2011
    Certifications & Approvals
    ATEXKEMA 10ATEX0147 X
    IECExKEM 10.0068X
    UKEXDEKRA 21UKEX0055X
    c FM usFM17US0004X / FM17CA0003X
    c UL us, UL 61010-1E314307
    EAC ExEAEU KZ 7500361.01.01.08756